If the abnormal phase has a normal output current and a significantly low output voltage, it is possible that the voltage line is loose or disconnected, and the voltage line needs to be replaced before testing.
Whether the grounding is good should be connected to the grounding grid inside the substation, and tower grounding devices or direct connection to the overhead ground wire leads should not be used.
The protective grounding column on the instrument panel and the N terminal of the test power output must be reliably grounded, and the tested circuit must be reliably grounded through a grounding knife switch during the wiring or disconnection process.
Before testing the mutual inductance, the induced voltage of the circuit should be measured to not exceed 750VAC.
Short circuit the power outputs A, B, and C with the voltage measurement UA, UB, and UC respectively.
P-level current transformers can determine whether the accurate limit factor KALF is qualified by measuring the excitation curve.