GKC433H Switchgear Analyzer
GKC433H Switchgear Analyzer GKC433H Switchgear Analyzer GKC433H Switchgear Analyzer

GKC433H Switchgear Analyzer

Tests the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.

Tests the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.

INSTRUCTION:

1. Test the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.

2. Test parameters including closing time, opening time, asynchronous time, bounce time, pre-insertion time, and operating-coordination time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.

3. Measure the pre-insertion time and resistance of 6 resistor contacts.

4. The panel is equipped with 12 contact status indicator lights to help determine closing/opening status and confirm correct wiring.

5. The system includes three analog transducer input channels and three digital transducer input channels. Measure stroke, penetration, rebound, overshoot time, overshoot, and operating speed of the switchgear using resistive transducers and digital transducers.

6. With digital transducers, the rotation angle of single-turn or multi-turn operating mechanisms can be measured accurately. Measurement resolution up to 0.04 degrees.

 

FEATURES:

1. Test the mechanical and electrical characteristics of various high-voltage circuit breakers, isolating switches, and contactors.
2. Test parameters including closing time, opening time, asynchronous time, bounce time, pre-insertion time, and operating-coordination time for 12 main contacts, 6 contacts with closing resistors, 6 main contacts, and 6 auxiliary contacts.
3. Measure the pre-insertion time and resistance of 6 resistor contacts.
4. The panel is equipped with 12 contact status indicator lights to help determine closing/opening status and confirm correct wiring.
5. The system includes three analog transducer input channels and three digital transducer input channels. Measure stroke, penetration, rebound, overshoot time, overshoot, and operating speed of the switchgear using resistive transducers and digital transducers.
6. Digital transducers enable accurate measurement of the rotation angle of single-turn or multi-turn operating mechanisms, with measurement resolution up to 0.04 degrees. This provides data for determining whether the switch operation is properly executed.
7. Using gyroscope transducers, no mounting brackets are required. Convenient and fast. (Optional)
8. Supports closing, opening, O-C-O, C-O, and O-C control sequences.
9. Able to test the mechanical characteristics of manually operated circuit breakers.
10. Edit and store 50 switch models with various speed definitions.
11. Change speed definitions and recalculate automatically after testing is completed.
12. Built-in high-power adjustable DC power supply, with manual and automatic voltage regulation modes.
13. Equipped with a manual voltage adjustment knob, a closing button, and an opening button, enabling quick close/open operations and action-voltage testing.
14. The built-in continuous-output DC power supply is used for motor energy storage.
15. Provides motor-current measurement. By analyzing the current of the circuit breaker or isolating switch motor, it can be determined whether the energy-storage system or the operating mechanism is abnormal.
16. Output control uses electronic switches, offering high control accuracy and long service life.
17. Six current sensors measure the current of the three-phase closing and opening coils respectively.
18. Provides the function for measuring the resistance of the closing and opening coils.
19. The instrument can store 500 sets of test data. Data is retained even in the event of a power failure.
20. Stored test data can be transferred to a USB drive.
21. Use a USB flash drive to upgrade the instrument software.
22. The LCD screen clearly displays the operation interface, test data, contact waveforms, travel curves, and current curves indoors and outdoors.
23. High-speed thermal printers can print test data, contact waveforms, travel curves, and current curves.
24. Supports up to 10,000 automatic operation tests.
25. A USB communication cable can be used to connect to a computer for operation.
26. Test data can be opened on a computer for analysis, envelope generation, and test report generation.
27. Equipped with a temperature sensor interface for measuring the operating-mechanism temperature.
28. Equipped with communication interfaces, allowing optional external dynamic resistance measurement, both-sides grounding tests, and graphite contact testing modules.
29. Adopts Bluetooth communication to meet the requirements of the State Grid “Technical Specification for Data and Communication of Digital Testing Instruments for Electrical Equipment”.
30. Supports online testing of Bluetooth 2.0 and above devices and extracts internal test data from the instrument. (Optional)
31. Provides an open Bluetooth communication protocol supporting secondary development of mobile devices. (Optional)
32. Selectable simplified Chinese and English operation interfaces.

 

SPECIFICATIONS:

1. Timing record length: 1–20000 ms. Accuracy: ±(0.05%T + 0.1) ms
Reference resolution: 1–2000 ms, resolution 0.1 ms; 2000–20000 ms, resolution 1 ms
2. Analog input measurement range: 0–5 V
3. Transducer resistance range: 50 Ω–5 kΩ
4. Digital transducer interface: RS422 interface
5. Digital transducer accuracy: ±0.1°; Resolution: 0.04°
6. Stroke measurement range: max. 1000 mm (depends on transducer length). Minimum resolution: 0.1 mm
7. Stroke measurement accuracy: ±(0.5%L + 0.2) mm
8. Speed measurement range: 0–20 m/s; Resolution: 0.01 m/s
9. DC output: 0–270 V / 20 A; Power: 4 kVA
10. DC voltmeter measurement range: 0–300 V; Accuracy: ±(0.5%U + 1) V
11. Coil current measurement range: DC 0–30 A; AC peak 0–30 A; Resolution: 0.01 A
Motor current measurement range: DC 0–4 A to 40 A; AC peak 0–4 A to 40 A; Resolution: 0.01 A
12. Coil resistance measurement range: 50–300 Ω; Resolution: 0.1 Ω; Accuracy: ±(1%R + 0.2) Ω
13. Resistive contact measurement range: 50–2000 Ω; Resolution: 1 Ω; Accuracy: ±(1%R + 1) Ω
14. Trigger voltage: ≥30 V
15. Output control power: 300 V / AC 30 A / DC
16. Power supply: AC 198–264 V, 47–63 Hz
17. Operating environment: -10°C to 50°C; Humidity ≤90% RH; No condensation
18. Dimensions: 492 mm × 392 mm × 218 mm
19. Weight: 12 kg

 